V198 Chemical injection systems
Written V0198 on the CMS-2567 and in QCOR.
Cited on this tag? What happens after a citation · One-page sheet for the binder
The regulation
ANSI/AAMI RD52:2004 Requirements as Adopted by Reference 42 CFR 494.40 (a)
5.2.6 Chemical injection systems
6.2.6 Chemical injection systems
5.2.6 Chemical injection systems
Chemical injection systems consist of a reservoir that contains the chemical to be injected, a metering pump, and a mixing chamber located in the main water line. Chemical injection systems also include some means of regulating the metering pump to control the addition of a chemical. This system should be designed to tightly control the addition of the chemical. The control system should ensure that a chemical is added only when water is flowing through the pretreatment cascade and that it is added in fixed proportion to the water flow or based on some continuously monitored parameter, such as pH, using an automated control system. If an automated control system is used to inject the chemical, the controlling parameter should be independently monitored. There should also be a means of verifying that the concentrations of any residuals arising from the chemical added to the water are reduced to a safe level before the water reaches its point of use.
When acid is added to adjust pH, a mineral acid should be used.
6.2.6 Chemical injection systems
Systems for chemical injection should be monitored according to the manufacturer’s instructions. If a facility designs its own system, procedures should be developed to ensure proper preparation of the chemical, adequate mixing of the injected chemical with the water flowing through the pretreatment cascade, and reduction to a safe level of the concentration of any chemical residuals before the point of water use. The facility should also verify that the injected chemical does not degrade the performance of downstream devices, including the primary purification process. The adequacy of these procedures must be verified using an independent laboratory. Verification can be accomplished by testing samples from the chemical reservoir and the water line after the point of injection for at least three batches of chemical.
When the chemical to be injected is prepared at a facility from powder or by dilution of a liquid concentrate, the chemical injection reservoir must be labeled with the name of the chemical and its concentration, the date the solution was prepared, and the name of the person who mixed the solution.
Each batch of chemical should be tested for correct formulation before use. A batch of chemical must not be used or transferred to the injection system reservoir until all tests are completed. The test results—and verification that they meet all applicable criteria—should be recorded and signed by the individual performing the tests.
Protective clothing and an appropriate environment, including ventilation adequate to meet applicable OSHA environmental exposure limits, should be provided when chemicals for injection are prepared in a dialysis facility.
CMS's interpretive guidance
Interpretive Guidelines § 494.40(a)
ANSI/AAMI RD52:2004 Requirements as Adopted by Reference 42 CFR 494.40(a)
5.2.5 Carbon adsorption
In some circumstances, carbon adsorption may not adequately remove chloramines from water. High pH of feed water, the occurrence of N-chloramines, and the use of orthophosphate or polyphosphate for corrosion control have been associated with a decrease in the removal of chloramines by carbon adsorption. In those situations, carbon adsorption may need to be supplemented with other methods of chloramine removal.
5.2.6 Chemical injection systems
Chemical injection systems may be used in the pretreatment section of a water purification system to supplement the physical purification processes described in the previous clauses. Applications of chemical injection include the addition of sodium metabisulfite to remove chloramines and the addition of acid to adjust pH.
Organic acids may act as nutrients, allowing bacteria to proliferate.
AAMI Rationale for the Development and Provision of This Recommended Practice
A.5.2.6 Chemical injection systems
The AAMI RDD Committee expressed reservations about adding chemicals to the water. However, it recognized that the addition of chemicals may be necessary in some circumstances if a facility is to meet the maximum contaminant levels set forth in AAMI 4.1.1. For example, if the municipal water contains high levels of N-chloramines or chloramine in the presence of orthophosphate or polyphosphate, injection of sodium metabisulfite may be one of the few options available for chloramine removal.
If chemical injection is used in the pretreatment cascade, users should ensure that the addition of the chemical does not interfere with the operation of subsequent purification processes, including the primary purification process. For example, the performance of thin-film composite reverse osmosis membranes may be affected by the pH of the feed water. At pH levels below 7, the rejection of fluoride may be substantially reduced compared to its rejection at a pH of 8.
Suggested monitoring guidelines from ANSI/AAMI RD52, Table 4 include: For chemical injection systems, monitor the level of chemical in the reservoir, injector function, and value of the controlling parameter (pH) daily. Results should indicate that the chemical level in the reservoir is greater than or equal to the facility's set value, and the controlling parameter is within the range of the facility's set values.
Additional Guidance:
There are other chemicals that may be injected to address problems with excessive chlorination or pH levels. If chemical injection is in use, facility policy must address this and reflect the manufacturer’s direction in the use of any system. If the acid is being used to lower pH, a monitor including an audible alarm in the treatment area should be used. If a flocculant is being injected to address excessive organic matter, an alarm will not be needed.
If the facility has designed its own system, the medical director should be cognizant of the risks and benefits of the system and is expected to have participated in the decision to install it. Verification of the function and safety of a self-designed chemical injection system must be completed prior to placing the system online during active patient treatment.
Labels must be updated at least every time a solution for use in the system is prepared.
The requirement for “testing of each batch” could be met by using a test specified by the manufacturer of the chemical or the injection device, such as pH or conductivity. “Verification that the test results meet all applicable criteria” means the person doing the test compares the test result with the expected result to ensure the test result is within the expected range(s). If the test result does not match the expected range, that batch of chemical must not be used. Policy should direct the next steps, including options such as mixing another batch and retesting, and notifying supervisory staff for direction.
The Hazard Communication Standard (HCS) (OSHA, 29 CFR 1910.1200(g)), revised in 2012, requires that the chemical manufacturer… provide Safety Data Sheets (SDSs) (formerly MSDSs or Material Safety Data Sheets) for each hazardous chemical to downstream users to communicate information on these hazards. Staff must follow the manufacturer provided SDS and implement protective measures related protective gear and ventilation necessary for preparation of chemicals for injection.
Chemical injection systems are not required in every facility; the source water should determine the water treatment components needed. If chemical injection is in use, the facility must follow these requirements.