V318 Reprocessing area and ventilation
Written V0318 on the CMS-2567 and in QCOR.
Cited on this tag? What happens after a citation · One-page sheet for the binder
The regulation
ANSI/AAMI RD47:2002/A1:2003 Requirements as Adopted by Reference 42 CFR § 494.50 (b)(1)
8 Physical plant and environmental safety considerations
8.1 Reprocessing area and ventilation
The reprocessing area should be designed to suit the operation carried out and maintain acceptable ambient concentrations of harmful substances (see Table 1). The area should be kept clean and sanitary. It may be part of the dialysis treatment area, as long as equipment used is properly designed and vented to meet the requirements for environmental safety (see [AAMI] 8.5).
| Substance/material | Limits (PEL)a |
|---|---|
| Acetic acid | 10 ppm TWAb |
| Chlorine dioxide (syn: chlorine oxide) | 0.1 ppm TWA |
| Citric acid | None developed |
| Formaldehyde | 0.75 ppm TWA 2 ppm STELc(15 min) 0.5 ppm action level |
| Glutaraldehyde | 0.2 ppm ceiling NIOSH/OSHA |
| Hydrogen peroxide | 1 ppm TWA |
| Peracetic acid | None developed |
| Phenol | 5 ppm TWA |
ppm = parts per million
a ) PEL (permissible exposure limit) represents the limit of what employees can be exposed to; PELs can be TWAs or STELs.
b ) TWA (time-weighted average) represents the limit of what an employee can be exposed to in an eight-hour period.
c ) STEL (short-term exposure limit) represents the limit of what an employee can be exposed to in any 15-minute time period.
CMS's interpretive guidance
Interpretive Guidance § 494.50(b)(1)
Although the equipment for air testing may not be kept on-site, it should be available for use if staff or patients complain about germicide vapors.
There should be a schedule for routine air-level testing for germicides vapors, along with references describing the safe exposure levels, and if there are any circumstances which would require an unscheduled test.
The reprocessing area must be kept clean and free of clutter. Blood splashes should be immediately cleaned and the affected surfaces disinfected.