V201 RO: chemical analysis at installation and yearly
Written V0201 on the CMS-2567 and in QCOR.
Cited on this tag? What happens after a citation · One-page sheet for the binder
The regulation
ANSI/AAMI RD52:2004 Requirements as Adopted by Reference 42 CFR 494.40(a)
6.2.7 Reverse osmosis: (Chemical analysis: frequency)
Chemical analysis for the contaminants listed in 4.1.1 (Table 1) should be done when the RO system is installed, when membranes are replaced, and at not less than annual intervals thereafter to ensure that the limits specified in 4.1.1 are met (see Table 1). Chemical analyses should be done when seasonal variations in source water suggest worsening quality or when rejection rates fall below 90%.
CMS's interpretive guidance
Interpretive Guidance § 494.40(a)
If your State has more stringent requirements, those must be followed to avoid potential noncompliance with 42 C.F.R. § 494.20..Accordingly, facilities who fail to comply with state and local laws would be cited at V100 or V101.
Connected tags
Tags whose guidance points here
https://middlemolecule.com/rulebook/tags/v201/