V214 UV irradiators in water storage and distribution

Written V0214 on the CMS-2567 and in QCOR.

Enforces ANSI/AAMI RD52:2004, adopted by reference at 42 CFR 494.40(a) · Appendix H Rev. 246, page 85 · checked 12 Nov 2026

Cited on this tag? What happens after a citation · One-page sheet for the binder

The regulation

ANSI/AAMI RD52:2004 Requirements as Adopted by Reference 42 CFR 494.40(a)

5.3.4 Bacterial control devices

5.3.4.1 Ultraviolet irradiators

Ultraviolet irradiators: When used to control bacterial proliferation in water storage and distribution systems, UV irradiation devices shall be fitted with a low-pressure mercury lamp that emits light at a wavelength of 254 nm and provides a dose of radiant energy of 30 milliwatt-sec/cm2, [except in the case described below]. The device shall be sized for the maximum anticipated flow rate according to the manufacturer's instructions. [ANSI/AAMI RD52:2004 requirements for UV irradiators intended for use in hemodialysis applications directs users to RD62:2001, Section 4.3.13]

5.3.4.1 Ultraviolet irradiators

If the irradiator includes a meter as described above, the minimum dose of radiant energy should be at least 16 milliwatt-sec/cm2.

To prevent the use of sublethal doses of radiation that may lead to the development of resistant strains of bacteria, UV irradiators shall be equipped with a calibrated ultraviolet intensity meter …or with an on-line monitor of radiant energy output that activates a visible alarm, which indicates that the lamp should be replaced. Alternatively, the lamp should be replaced on a predetermined schedule according to the manufacturer’s instructions to maintain the recommended radiant energy output.

6.3.4 Bacterial control devices

6.3.4.1 Ultraviolet irradiators

Ultraviolet irradiators intended for use as a direct means of bacterial control shall be monitored for radiant energy output. UV irradiators should be monitored at the frequency recommended by the manufacturer. A log sheet should be used to indicate that monitoring has been performed.

CMS's interpretive guidance

Interpretive Guidance § 494.40(a)

ANSI/AAMI RD52:2004

5.3.4 Bacterial control devices

5.3.4.1 Ultraviolet irradiators

[Equipment]

The recommendations provided in this clause concern UV irradiators used specifically for bacterial control.

Ultraviolet irradiators (also known as UV lights) may be used to control bacterial proliferation in purified water storage and distribution systems. UV irradiators contain a low-pressure mercury lamp that emits ultraviolet light at a wavelength of 254 nm. The lamp is housed in a transparent quartz sleeve that isolates it from direct contact with the water. If the irradiator is not fitted with a calibrated ultraviolet intensity meter that is filtered to restrict its sensitivity to the disinfection spectrum and that is installed in the wall of the disinfection chamber at the point of greatest water depth from the lamp, the dose of radiant energy provided by the lamp shall be at least 30 milliwatt-sec/cm2.

6.3.4 Bacterial control devices

6.3.4.1 Ultraviolet irradiators

[Monitoring]

UV irradiators are available equipped with radiant energy intensity sensors. A visual alarm or an output meter is acceptable for determining if the UV lamp is emitting sufficient radiant energy.

Because the radiant energy decreases with time, annual lamp replacement is typically required. Periodic cleaning of the quartz sleeve may also be required, depending on the water quality.

Additional Guidance:

Monitoring may be accomplished by any of the following options: use of a meter to monitor intensity of the lamp, use of an on-line monitor that activates an alarm, or replacement on a predetermined schedule.

The use of a UV irradiator in a bicarbonate distribution system may have a totally different role. If ozone is used to disinfect that system, the UV irradiator may be used to break down the ozone. If the UV irradiator is part of the bicarbonate distribution system, responsible staff must be able to describe the intended purpose of the UV in that application. Monitoring of the irradiator is still required, but there is no need to follow an irradiator used in the bicarbonate distribution system with an ultrafilter or other endotoxin-retentive device.

Verbatim from Appendix H Rev. 246, with CMS's headings, lists and bold. Check page 85 (the full 469-page PDF) before quoting it.