V213 Distribution loop: bacteria and endotoxin testing
Written V0213 on the CMS-2567 and in QCOR.
Cited on this tag? What happens after a citation · One-page sheet for the binder
The regulation
ANSI/AAMI RD52:2004 Recommendations as Adopted by Reference 42 CFR 494.40(a)
6.3.3 Water distribution systems (bacteria and endotoxin testing)
Water distribution piping systems should be monitored for bacteria and endotoxin levels. Bacteria and endotoxins shall not exceed the levels specified in [AAMI] 4.1.2. [(i.e., bacteria <200 CFU/mL and endotoxin <2 EU/mL]
Bacteria and endotoxin testing should be conducted at least monthly. For a newly-installed water distribution piping system, or when a change has been made to an existing system, it is recommended that weekly testing be conducted for 1 month to verify that bacteria or endotoxin levels are consistently within the allowed limits.
Monitoring should be accomplished by taking samples from the first and last outlets of the water distribution loop and the outlets supplying reuse equipment and bicarbonate concentrate mixing tanks. If the results of this testing are unsatisfactory, additional testing (e.g., ultrafilter inlet and outlet, RO product water, and storage tank outlet) should be undertaken as a troubleshooting strategy to identify the source of contamination, after which appropriate corrective actions can be taken.
Bacteria and endotoxin levels shall be measured as specified in ANSI/AAMI RD62:2001 (see 2.3).
All bacteria and endotoxin results should be recorded on a log sheet to identify trends that may indicate the need for corrective action.
CMS's interpretive guidance
Interpretive Guidance § 494.40(a)
ANSI/AAMI RD52:2004
7.2 Microbial monitoring methods
7.2.1 General
Additional testing, such as at the end of the water purification cascade and at the outlet of the storage tank, if one is used, may be necessary during initial qualification of a system or when troubleshooting the cause of contamination within the distribution loop.
Suggested water distribution piping system monitoring guidelines from ANSI/AAMI RD52 6.1, Table 4 include:
Measure bacterial growth and pyrogens, weekly, until a pattern of consistent compliance can be demonstrated, then monthly. Action levels for bacterial growth are >50 CFU/mL; for endotoxin >1 EU/mL.
Additional Guidance:
An example of a change to the existing system would be changes to the RO membranes or installation of a new storage tank. Changes to the pre-treatment components (e.g., sediment filters, cartridge filters, softener, or carbon tanks) do not require a period of more frequent testing.
The sites listed should be cultured routinely, with additional sites considered if the results of routine test sites indicate a problem.
The bacteria and endotoxin results log, referred to in 6.3.3: Water distribution systems, could be graphic reports or documents generated by the laboratory, or created by staff from laboratory data, in order to include results from multiple months to allow identification of trends.
V252 should be used when routine cultures/endotoxin testing is not done at least monthly. Use this tag if more frequent testing is not done when indicated (e.g., for new facilities, when a major change has been made to an existing water system, or when monthly cultures taken from several sites are repeatedly positive).
Note: refer to V276 for requirements for preconfigured systems.
https://middlemolecule.com/rulebook/tags/v213/